Opens in a new tab
Cable Sizing

Sheath Induced Voltage and Circulating Current in Single-Core Cables

How to estimate sheath induced voltage, capacitive current and circulating current in bonded single-core cable systems.

Updated May 27, 2026

In three-phase single-core cable systems, metallic sheaths or armour can have voltage induced in them by the conductor currents. If the sheath or armour is unbonded, or bonded at one end only, the result is an induced voltage at the open end. If both ends are bonded, the induced voltage can drive circulating current in the sheath or armour.

This article sets out a calculation method for estimating sheath induced voltage and circulating current. Although the wording refers to sheaths, the same principles can be applied to armour where the armour forms a metallic return path.

The topic is closely related to Cable Sheath and Armour Losses, because circulating sheath or armour current can add heat and reduce cable current rating.

Induced voltage

The inductive voltage induced per unit length in the sheath of a single-core cable is given by:

Sheath induced voltage and circulating current equation 00

with:

Sheath induced voltage and circulating current equation 01
Sheath induced voltage and circulating current equation 02

For a three-phase set of single-core cables, the method can be expanded to calculate the induced sheath voltage for each phase:

Sheath induced voltage and circulating current equation 03
Sheath induced voltage and circulating current equation 04
Sheath induced voltage and circulating current equation 05

The mutual reactance terms depend on the cable spacing and arrangement:

Sheath induced voltage and circulating current equation 06
Sheath induced voltage and circulating current equation 07
Sheath induced voltage and circulating current equation 08
Sheath induced voltage and circulating current equation 09

Circulating currents

Sheath current has two main components:

  • Capacitive current: the conductor and sheath, separated by the insulation dielectric, act as a capacitor. Capacitive current flows from the conductor into the sheath and then to earth.
  • Inductive current: when sheaths are bonded at both ends, transformer coupling between the conductor and sheath drives a circulating current through the bonded metallic path.

Capacitive current

For a single-core cable, the capacitance is:

Sheath induced voltage and circulating current equation 10

Leakage current in the insulation can usually be ignored. The capacitive current for each phase per unit length is then:

Sheath induced voltage and circulating current equation 11
Sheath induced voltage and circulating current equation 12
Sheath induced voltage and circulating current equation 13

For sheaths bonded to earth at one end only, the total capacitive current is found by multiplying the per-unit-length value by the cable length. Where sheaths are bonded to earth at both ends, the capacitive current can flow towards earth in two directions. A simple estimate assumes the current divides equally between the two ends.

Inductive current

If the sheath is bonded at only one end, no inductive circulating current can flow. For sheaths bonded at both ends, the inductive circulating current is estimated by dividing the induced sheath voltage by the sheath impedance:

Sheath induced voltage and circulating current equation 14

The sheath resistance can be estimated from:

Sheath induced voltage and circulating current equation 15

with the temperature-adjusted sheath resistivity given by:

Sheath induced voltage and circulating current equation 16

The sheath reactance depends on the cable configuration. For cables bonded at both ends, the following approximations can be used:

  • Trefoil formation:
Sheath induced voltage and circulating current equation 17
  • Flat formation, no transposition:
Sheath induced voltage and circulating current equation 18
  • Flat formation, regular transposition:
Sheath induced voltage and circulating current equation 17

Sheath voltage and current calculations are sensitive to conductor current, cable construction, installation geometry and any deliberate or accidental parallel current paths. The results from this simplified method should be treated as indicative of magnitude rather than exact measured values.

Cross bonding and transposition

Cross bonding and cable transposition are used to reduce sheath induced voltage and circulating current. Over three sections, the induced voltages are phase shifted by approximately 120 degrees; summing the phase-shifted voltages reduces the overall induced voltage and the resulting circulating current.

Cable cross bonding and transposition diagram
Cross bonding and transposition of single-core cables.

For balanced cables installed in trefoil formation, sheath currents are symmetrical and cross bonding of the sheaths may be sufficient. For flat formation, the induced voltages vary by phase, so cable transposition is normally needed to balance the induced voltages.

References

  1. Moore, G. Electric Cables Handbook/BICC Cables. Oxford: BSCI, 2000.
  2. Chen, Wu, Cheng and Yan. Sheath Circulating Current Calculations and Measurements of Underground Power Cables. Xi’an Jiaotong University.
  3. IEC 60287-1-1, Electric cables – Calculation of the current rating – Current rating equations and calculation of losses.

Symbols

AsCross-sectional area of sheath, m2
CCapacitance, F/m
dcDiameter of the conductor, m
dsInside diameter of the sheath, m
fFrequency, Hz
ICable conductor current, A
I1, I2, I3Conductor phase currents of L1, L2 and L3, A
Is1, Is2, Is3Sheath phase currents of L1, L2 and L3, A
LsSheath inductance, H/m
RsSheath resistance, ohm/m
SDistance between cable centres, m
S12, S23, S31Distances between phase cable centres, m
tsSheath thickness, m
X1, X3, Xa, XbReactance formula terms, ohm/m
XmMutual reactance between conductor and sheath, ohm per unit length
XsSheath reactance, ohm/m
UsSheath voltage, V
U1, U2, U3Phase voltages of L1, L2 and L3, V
Us1, Us2, Us3Sheath inductive phase voltages of L1, L2 and L3, V
αsTemperature coefficient of sheath resistivity, per degree C
ηSheath/conductor temperature ratio, typically 0.7 to 0.8
ε0Permittivity of free space, 8.854187819 x 10-12 F/m
εrRelative permittivity of the dielectric
θService temperature of conductor, degree C
ρsResistivity of sheath, ohm.m
ωAngular frequency, 2πf, s-1
   

Related Articles