Metric to AWG Cable Size Conversion Table

Metric to AWG and MCM conductor size conversion table with circular mils, stranding and approximate overall diameter.

Updated May 27, 2026

This reference table gives approximate conversions between metric conductor sizes and American Wire Gauge (AWG), circular mils and common stranding arrangements.

The values are useful for comparing conductor sizes, but metric and AWG/MCM sizes are not always exact substitutes. Final cable selection should use the applicable standard, current rating, resistance, voltage drop and installation requirements.

Definitions

Circular milsCross-sectional area expressed in circular mils.
AWGAmerican Wire Gauge size.
mm2Metric conductor cross-sectional area.
MCMThousand circular mils, also commonly written kcmil.

Metric AWG conversion table

Metric size, mm2AWG / MCMCircular milsStrands / strand dia., inchStrands / strand dia., mmApprox. overall dia., inchApprox. overall dia., mm
0.59871/.0321/.8130.0320.81
2010207/.01217/.3070.0360.91
0.7514801/.0391/.9910.0390.99
1816201/.04031/1.020.041.02
1816207/.01527/.3860.0461.16
119741/.0451/1.140.0451.14
119747/.0177/.4320.0511.3
1625801/.05081/1.290.0511.29
1625807/.01927/.4880.0581.46
1.529601/.0551/1.400.0551.4
1.529607/.0217/.5330.0631.6
1441101/.06411/1.630.0641.63
1441107/.02427/.6150.0731.84
2.549341/.0711/1.800.0711.8
2.549347/.0277/.6860.0812.06
1265301/.08081/2.050.0812.05
1265307/.03057/.7750.0922.32
478941/.0891/2.260.0892.26
478947/.0347/.8640.1022.59
10103801/.10191/2.590.1022.59
10103807/.03857/.9780.1162.93
6118401/.1091/2.770.1092.77
6118407/.0427/1.070.1263.21
9130901/.11441/2.910.11442.91
9130907/.04327/1.100.133.3
8165101/.12851/3.260.1283.26
8165107/.04867/1.230.1463.7
10197401/.1411/3.580.1413.58
10197407/.0547/1.370.1624.12
7208201/.14431/3.670.1443.67
7208207/.05457/1.380.1644.15
6262401/.1621/4.110.1624.11
6262407/.06127/1.550.1844.66
16315807/.0687/1.730.2045.18
5330907/.06887/1.750.2065.24
4417407/.07727/1.960.2325.88
25493407/.0857/2.160.2556.48
254934019/.05219/1.320.266.6
3526207/.08677/2.200.266.61
2663607/.09747/2.470.2927.42
35690707/.1007/2.540.37.62
356907019/.06119/1.550.3057.75
18369019/.066419/1.690.3329.43
509868019/.07319/1.850.3659.27
1/010560019/.074519/1.890.3739.46
2/013310019/.083719/2.130.41910.6
7013810019/.08619/2.180.4310.9
3/016780019/.09419/2.390.4711.9
3/016780037/.067337/1.710.47112
9518750019/.10119/2.570.50512.8
9518750037/.07237/1.830.50412.8
4/021160019/.105519/2.680.52813.4
120238 MCM37/.08137/2.060.56714.4
250 MCM37/.082237/2.090.57514.6
150300 MCM37/.09037/2.290.6316
350 MCM37/.097337/2.470.68117.3
185365 MCM37/.10037/2.540.717.8
400 MCM37/.10437/2.640.72818.5
240474 MCM37/.11437/2.900.79820.3
240474 MCM61/.08961/2.260.80120.3
500 MCM37/.116237/2.950.81320.7
500 MCM61/.090561/2.300.81420.7
300592 MCM61/.09961/2.510.89122.6
600 MCM61/.099261/2.520.89322.7
700 MCM61/.107161/2.720.96424.5
750 MCM61/.110961/2.820.99825.4
750 MCM91/.090891/2.310.99925.4
400789 MCM61/.11461/2.901.02626.1
800 MCM61/.114561/2.911.03126.2
800 MCM91/.093891/2.381.03226.2
5001000 MCM61/.128061/3.251.15229.3
1000 MCM91/.104891/2.661.15329.3
6251234 MCM91/.11791/2.971.28732.7
1250 MCM91/.117291/2.981.28932.7
1250 MCM127/.0992127/2.521.2932.8
1500 MCM91/.128491/3.261.41235.9
1500 MCM127/.1087127/2.761.41335.9
8001579 MCM91/.13291/3.351.45236.9
10001974 MCM91/.14791/3.731.61741.1
2000 MCM127/.1255127/3.191.63241.5
2000 MCM169/.1088169/2.761.63241.5

For resistance and cable-sizing calculations using conductor area, see Conductor Resistance, Electrical Resistivity and Cable Sizing.

For the standard metric conductor size sequence used in IEC-based cable design, see standard cable sizes to IEC 60228.

   