Opens in a new tab
Cable Sizing

The Adiabatic Equation and k Factor for Cable Thermal Withstand

How to use the adiabatic equation for cable short-circuit thermal withstand calculations, including k factor values and material constants.

Updated September 5, 2026

When calculating the fault rating of a cable, it is generally assumed that the fault duration is short enough that no heat is dissipated from the cable to its surroundings. This adiabatic assumption simplifies the calculation and is normally conservative.

The adiabatic equation is used to check whether a cable conductor has enough cross-sectional area to withstand a short-circuit current for the protective device operating time. The factor k connects that equation to conductor material, insulation type and permissible temperature rise.

Adiabatic equation

For a fault current I lasting for time t, the minimum required conductor cross-sectional area is:

   

A=I2tk

ANominal conductor cross-sectional area, mm2
IFault current, A
tDuration of fault current, s
kFactor dependent on conductor material, insulation type and temperature limits

Alternatively, if the cable cross-sectional area and fault current are known, the maximum allowable disconnection time is:

t=k2A2I2

Typical k values

The factor k depends on the cable insulation, allowable temperature rise during the fault, conductor resistivity and conductor heat capacity. Typical values are shown below.

Insulation typeInitial temperature, °CFinal temperature, °CCopperAluminiumSteel
Thermoplastic 70 °C (PVC)70160 / 140115 / 10376 / 7842 / 37
Thermoplastic 90 °C (PVC)90160 / 140100 / 8666 / 5736 / 31
Thermosetting 90 °C (XLPE, EPR)902501439452
Thermosetting 60 °C (rubber)602001419351
Thermosetting 85 °C (rubber)852201348948
Thermosetting 185 °C (silicone rubber)1803501328747
Where two values are shown, the lower value applies to conductor cross-sectional areas greater than 300 mm2. Values are suitable for durations up to 5 seconds. Source: BS 7671 and IEC 60364-5-54.

Calculating k from material properties

IEC 60364-5-54 gives the following formula for calculating k:

k=Qc(β+20)ρ20lnβ+θfβ+θi

QcVolumetric heat capacity of the conductor at 20 °C, J·K-1·mm-3
βReciprocal of the temperature coefficient of resistivity at 0 °C
ρ20Electrical resistivity of conductor material at 20 °C, Ω·mm
θiInitial conductor temperature, °C
θfFinal conductor temperature, °C

Strictly speaking, β is specified at 0 °C. In myCableEngineering calculations, β is determined by taking the reciprocal of the 20 °C temperature coefficient. This introduces a small but negligible error.

Material constants

Conductor materialβ, °CQc, J·K-1·mm-3ρ20, Ω·mm
Copper234.53.45 × 10-317.241 × 10-6
Aluminium2282.5 × 10-328.267 × 10-6
Steel2023.8 × 10-3138 × 10-6

Simplified conductor equations

Substituting the values above and rearranging the IEC equation gives the following practical forms.

Copper conductors:

k=226ln(1+θf−θi234.5+θi)

Aluminium conductors:

k=148ln(1+θf−θi228+θi)

Steel conductors:

k=78ln(1+θf−θi202+θi)

Example

Consider a maximum fault current of 13.6 kA where the protective device trips in 2.6 s. For a copper thermosetting 90 °C cable, use k = 143. The minimum safe cable cross-sectional area is:

   

S=136002×2.6143=154mm2

Any selected conductor larger than this value will withstand the fault on the basis of the adiabatic calculation. Thermal withstand is one part of cable selection. Explore project-based cable sizing with myCableEngineering to review fault withstand alongside current capacity and voltage drop.

Derivation of the adiabatic equation

The term adiabatic describes a process with no heat transfer. For cable faults, this assumes that all heat generated during the fault is retained in the conductor rather than dissipated away. This is not completely true in practice, but it is generally conservative.

From physics, the heat Q required to raise a material by ΔT is:

Q=c m ΔT

QHeat added, J
cSpecific heat constant of the material, J·g-1·K-1
mMass of the material, g
ΔTTemperature rise, K

The energy into the cable during a fault is:

Q=I2R t

From the physical properties of the cable conductor:

m=ρcA l

and

R=ρrlA

ρcMaterial density, g/mm3
ρrResistivity of the conductor, Ω·mm
lCable length, mm

Combining these terms:

I2Rt=cm ΔT

I2tρrlA=c ρcA l ΔT

Rearranging for area gives:

S=I2tk

where

k=cρcΔTρr

The maximum allowable temperature rise is:

ΔT=θf−θi

θfFinal, or maximum, cable insulation temperature, °C
θiInitial operating cable insulation temperature, °C

The equations above use grams and square millimetres rather than kilograms and metres. This convention is widely used by cable specifiers; the equations can be reformulated in SI base units if required.

   

Related Articles