Use the link on the left to access our cable sizing application. Manage and size all your cables, from low voltage to 33 kV.
Voltage drop is calculated in accordance with CENELEC technical report CLC/TR 50480 "Determination of cross-sectional area of conductors and selection of protective devices", dated February 2011.
The voltage drop (as a percentage) is given by:
ΔU= b( Rcosφ+Xsinφ ) I b U o ⋅100
where ΔU = cable voltage drop, % Uo = nominal line to neutral voltage, V R = cable resistance, Ω X = cable reactance, Ω Ib = cable design current, A b = circuit factor (=2 for d.c. and single-phase, =1 for three-phase)
Note: within myCableEngineering, we use complex arithmetic and the above is evaluated as:
ΔU= b( R+jX ) I b U o ⋅100
Note: R and X are per line conductor. For example, the resistance of a single-phase two core circuit (live and neutral) would be 2R (assuming the live and neutral circuits are of equal resistance). For parallel cables, R and X are the per line resultant values. For example, nph cables in parallel, with the resistance of one line conductor is Rc0ph then the R = Rc0ph/nph.
The above equation), has the relative voltage drop expressed as a percentage of Uo. Multiplying by Uo will give the actual voltage drop for d.c. and single-phase circuits and for three-phase circuits, this needs to be multiplied by √3.
Adjusting the CENELEC equation to take into account referring the voltage drop to line-line voltage for three-phase systems, setting R, X in ohms, and using complex forms gives:
- the resistance of a single conductor, Ω/m - the reaction of a single conductor, Ω/m - the impedance of single conductor , Ω/m - cable design current, A - the nominal line to neutral/earth voltage (for single-phase a.c. or d.c.), V - the nominal line to line voltage (for three-phase systems), V