Cable Sizing

Cable Impedance: Positive and Zero Sequence Calculations

Cable impedance formulae for positive and zero sequence calculations, including IEC 60909 arrangements with and without metallic sheaths or shields.

Updated May 27, 2026

Cable impedance is central to voltage drop, power loss, short-circuit current and earth-fault calculations. In many cases cable impedance can be calculated using IEC 60909-2, Short-circuit currents in three-phase a.c. systems – Part 2: Data of electrical equipment for short-circuit current calculations.

IEC 60909-2 gives formulae for single-core and multicore cables, with or without metallic sheaths or shields. Where a particular arrangement is not covered directly, the fundamental inductance and reactance relationships can be used to derive a suitable approximation.

Fundamental equations

For a single conductor, the internal self-inductance due to its own magnetic field is:

L=μ08π

The corresponding reactance is:

X=ωL=ωμ08π
μ0Permeability of free space, 4π x 10-7 N/A2
LSelf-inductance, H/m
XReactance, ohm/m
ωAngular frequency, 2πf

For a second external conductor, the inductance due to the field from the other conductor is:

Le=μ02πlndr

For two parallel conductors, the total inductance and reactance of one conductor are:

Lt=L+Le=μ08π+μ02πlndr=μ02π14+lndr Xt=ωμ02π14+lndr

Where conductor spacing varies, geometric mean spacing can be used. For three single-core cables in flat formation:

d=dL1L2×dL2L3×dL1L33

For more background, see Geometric Mean Distance.

Zero sequence impedance

The fundamental equations above are suitable for positive sequence impedance. Zero sequence impedance is more difficult because the return path can include neutral conductors, cable sheaths, armour, screens, earth and nearby metallic structures. IEC 60909 formulae are normally used directly for practical calculations.

For some zero sequence calculations it is necessary to consider equivalent soil penetration depth:

δ=1.851ωμ0ρ
δEquivalent soil penetration depth, m
ρSoil resistivity, ohm.m
μ0Permeability of free space, H/m

Cables without metallic sheaths or shields

Single-core cables

Three single-core cables without metallic sheath or shield.
Three single-core cables without metallic sheath or shield.

Positive sequence impedance, phase or neutral:

Z1=RL+jωμ02π14+lndrL

Zero sequence impedance, current return through earth:

Z0=RL+3ωμ08+jωμ02π14+3lnδrLd23

Zero sequence impedance, current return through fourth conductor:

Z0=4RL+j4ωμ02π14+lndLN3rLd

Zero sequence impedance, current return through fourth conductor and earth:

Z0=Z(0)113ωμ08+jωμ02πlnδdLN2RL+ωμ08+jωμ02π14+lnδrL

Multicore cables

Multicore cable without metallic sheath or shield.
Multicore cable without metallic sheath or shield.

For a three-core or four-core cable without metallic sheath or shield, the positive sequence impedance uses the same form as the single-core positive sequence equation above.

Zero sequence impedance, current return through full-size fourth conductor:

Z0=4RL+j4ωμ02π14+lndrL

Zero sequence impedance, current return through reduced-size fourth conductor:

Z0=RL+3RN+jωμ02π1+4lndLN3rLrN34d

Zero sequence impedance, current return through full-size fourth conductor and earth:

Z0=Z(0)113ωμ08+jωμ02πlnδdLN2RL+ωμ08+jωμ02π14+lnδrL

Zero sequence impedance, current return through reduced-size fourth conductor and earth:

Z0=Z(0)113ωμ08+jωμ02πlnδdLN2RN+ωμ08+jωμ02π14+lnδrN

Cables with metallic sheaths or shields

Single-core cables

Three single-core cables with metallic sheath or shield.
Three single-core cables with metallic sheath or shield.

Positive sequence impedance for cables bonded at both ends:

Z1=Z(1)10+ωμ02πlndrSm2Rs+jωμ02πlndrSm

IEC 60909 does not give a direct equation for zero sequence impedance with current return through shield only in this case.

Zero sequence impedance, current return through shield and earth:

Z0=Z(0)113ωμ08+j3ωμ02πlnδrSmd232Rs+3ωμ08+j3ωμ02πlnδrSmd23

Multicore cables

Multicore cable with metallic sheath or shield.
Multicore cable with metallic sheath or shield.

For a three-core or four-core cable with metallic sheath or shield, the positive sequence impedance uses the same positive sequence form as equation 10.

Zero sequence impedance, current return through screen:

Z0=RL+3RS+jωμ02π14+3lnrSmrLd23

Zero sequence impedance, current return through screen and earth:

Z0= Z(0)113ωμ08+jωμ02πlnδrSm2RS+ωμ08+jωμ02πlnδrSm

Zero sequence impedance, current return through fourth conductor and screen:

Z0=RL+jωμ02π14+3lndLNrL d23+3RN+jωμ02π14+lndLNrNRS+jωμ02πlnrSmdLNRN+RS+jωμ02π14+lnrSmrN

Zero sequence impedance, current return through fourth conductor, screen and earth:

Z0=Z(0)1113ZNZLS2+ZSZLN22ZLNZLSZNSZNZSZNS2

With:

ZN=RN+ωμ08+jωμ02π14+lnδrN ZS=RS+ωμ08+jωμ02πlnδrSm ZL123N=ZLN=3ωμ08+j3ωμ02πlnδdLN ZL123S=ZLS=3ωμ08+j3ωμ02πlnδrSm ZNS=wμ08+jωμ02πlnδrSm

Zero sequence impedance is strongly affected by cable construction, bonding, sheaths, armour, soil, pipes, nearby steelwork and other return paths. Dependable zero sequence values are often best obtained by measurement on the installed cable system.

Symbols

dGeometric mean spacing, line-to-line, m
dLNGeometric mean spacing, line-to-neutral, m
RLConductor resistance, ohm or ohm/m
RNNeutral or fourth conductor resistance, ohm or ohm/m
RSMetallic sheath or screen resistance, ohm or ohm/m
μ0Permeability of free space, 4π x 10-7 H/m
rLRadius of the conductor, m
rNRadius of the neutral or fourth conductor, m
rSmMean radius of sheath or shield, 0.5(rSi + rSa), m
δEquivalent soil penetration depth, m

Related topics

For applications of impedance in cable calculations, see Voltage Drop, IEC 60909 Fault Calculations and Earth Fault Loop Impedance.

Related Articles