IEC 60909 gives a method for calculating short-circuit currents in three-phase a.c. systems. It is commonly used to estimate maximum and minimum fault levels for switchgear rating, protection settings and cable withstand checks.
This article summarises the formulae used for faults far from generators. It sits under the wider Fault Current Calculations topic and links to Earth Fault Loop Impedance where IEC 60909 sequence values are used in cable calculations.
Short-circuit current formulae
For most components other than synchronous machines, the negative sequence impedance Z2 can often be taken as equal to the positive sequence impedance Z1.
| Fault type | Three-phase system | Single-phase system | D.C. system |
|---|---|---|---|
| Three-phase short circuit | – | – | |
| Line-to-line short circuit | |||
| Line-to-line-earth short circuit | – | – | |
| Line-earth short circuit |
For a single-phase system, a line-to-line fault is equivalent to a line-neutral fault. For a d.c. system, it is equivalent to a positive-to-negative fault.
For several series circuits in the fault loop, the final fault current can be calculated from the sum of the series impedances:
For d.c. circuits:
Source impedance
The source or external network impedance ZQ can be calculated from the short-circuit current. For three-phase and single-phase systems:
For d.c. systems:
Maximum and minimum fault levels
Both maximum and minimum fault levels are normally required. Maximum fault current is used for equipment short-circuit ratings. Minimum fault current is used to confirm that protective devices operate correctly under the least favourable fault condition.
- Use cmax or cmin as appropriate.
- When calculating external network impedance ZQ, use the maximum or minimum short-circuit current as appropriate.
- IEC 60909 recommends resistance at 20 °C for maximum short-circuit current, and resistance at end-of-short-circuit temperature for minimum short-circuit current.
- User-entered fault levels are commonly treated as values with voltage factor c = 1.
In myCableEngineering, conductor operating temperature is used as the reference for both maximum and minimum fault levels.
Voltage factor
| Nominal voltage Un | cmax for maximum short-circuit current | cmin for minimum short-circuit current |
|---|---|---|
| Low voltage, 100 to 1000 V | 1.05 | 0.95 |
| Medium voltage, 1 kV to 33 kV | 1.10 | 1.00 |
| High voltage, above 35 kV | 1.10 | 1.00 |
Symbols
| c | Voltage factor |
| Ik″ | Initial symmetrical three-phase short-circuit current, r.m.s., A |
| Ik1″ | Line-to-earth short-circuit current, A |
| Ik2″ | Line-to-line short-circuit current, A |
| IkE2E″ | Line-to-line-earth short-circuit current, A |
| Un | Nominal system voltage, line-to-line r.m.s., V; positive-negative voltage for d.c. systems |
| Z1 | Positive-sequence short-circuit impedance, ohm |
| Z2 | Negative-sequence short-circuit impedance, ohm |
| Z0 | Zero-sequence short-circuit impedance, ohm |
| ZQ | Impedance of an external network, ohm |
For converting upstream fault level data into source impedance, see Network Fault Level.
For estimating a transformer secondary source fault level before IEC 60909 network calculations, see Transformer Secondary Fault Level.
For the cable sequence impedance inputs used by IEC 60909, see Cable Impedance.
