Thermal Withstand

Last updated on 2016-10-21 1 mins. to read

When selecting a cable, the performance of the cable under fault conditions is an important consideration. It is important that calculations be carried out to ensure that any cable is able to withstand the effects of any potential fault or short circuit.  This note looks at how to do this.

The primary concern with cables under a fault condition is the heat generated, and any potential negative effect this may have on the cable insulation. 

Calculation of fault rating is based on the principle that the protective device will isolate the fault in a time limit such that the permitted temperature rise within the cable will not be exceeded.

In addition to the direct heating effect of fault currents, other considerations include:

  • electro-mechanical stress and fault levels large enough to cause cable failure
  • performance of joint and terminations under fault conditions

Comments

The adiabatic equation

Last updated on 2016-10-21 5 mins. to read

When calculating the fault ratings of a cable, it is generally assumed that the duration is short enough that no heat is dissipated by the cable to the surrounding.  Adopting this approach simplifies the calculation and errs on the safe side.

The normally used equation is the so-called adiabatic equation.  For a given fault of I, which lasts for time t, the minimum required cable cross-sectional area is given by:

  A= I 2 t k

where: A - the nominal cross-section area, mm2
I - the fault current in, A
t -  duration of fault current, s
k - a factor dependant on cable type (see below)

Alternatively, given the cable cross-section and fault current, the maximum time allowable for the protective device can be found from:

  t= k 2 A 2 I 2

The factor k is dependant on the cable insulation, allowable temperature rise under fault conditions, conductor resistivity and heat capacity.  Typical values of k are:

  Temperature Conductor Material
  Initial °C Final°C Copper Aluminium Steel
Thermoplastic 70°C (PVC)
 

70

160/140

115/103

76/78

42/37

Thermoplastic 90°C (PVC)

90

160/140

100/86

66/57

36/31

Thermosetting, 90°C (XLPE, EDR)

90

250

143

94

52

Thermosetting, 60°C (rubber)

60

200

141

93

51

Thermosetting, 85°C (rubber)

85

220

134

89

48

Thermosetting, 185°C (silicone rubber)

180

350

132

87

47

*where two values; lower value applied to conductor CSA > 300 mm2
* these values are suitable for durations up to 5 seconds, source: BS 7671, IEC 60364-5-54

Example

Consider a maximum fault current of 13.6 kA and the protective device trips in 2.6 s.  The minimum safe cable cross sectional area of a copper thermosetting 90°C cable (k=143) is:

 

  S= 13600 2 ×2.6 143 =154 mm 2

Any selected cable larger than this will withstand the fault.

Derivation  - Adiabatic Equation and k

The term adiabatic applies to a process where there is no heat transfer.  For cable faults, we are assuming that all the heat generated during the fault is contained within the cable (and not transmitted away).  Obviously, this is not fully true, but it is on the safe side.

From physics, the heat Q, required to rise a material ΔT is given by:

  Q=c m ΔT

where Q - heat added, J
c - specific heat constant of the material, J.g-1.K-1
m - mass of the material, g
ΔT - temperature rise, K

The energy into the cable during a fault is given by:

  Q= I 2 R t

where  R - the resistance of the cable, Ω

From the physical cable properties, we can calculate m and R as:

  m= ρ c A l    and      R= ρ r l A

where ρc - material density in g.mm-3
ρr - resistivity of the conductor, Ω.mm
l - length of the cable, mm

Combining and substituting we have:

  I 2 Rt=cm ΔT

  I 2 t ρ r l A =c ρ c A l ΔT

and rearranging for A gives:

  S= I 2 t k    by letting     k= c ρ c ΔT ρ r

Note: ΔT is the maximum allowable temperature rise for the cable:

  ΔT= θ f θ i

where θf - final (maximum) cable insulation temperature, °C
θi - initial (operating) cable insulation temperature, °C

Units:  are expressed in g (grams) and mm2, as opposed to kg and m.  This is widely adopted by cable specifiers.  The equations can easily be redone in kg and m if required.

Comments

Calculation of k Factor

Last updated on 2016-10-21 2 mins. to read

IEC 60364-5-54 gives the following formula for the calculation of the factor k:

k=Qc(β+20)ρ20lnβ+θfβ+θi

where Qc = volumetric heat capacity of conductor at 20°C, J.K-1.mm-3
ß = reciprocal of temperature coefficient of resistivity at 0 °C 
ρ20 =  electrical resistivity of conductor material at 20 °C, Ω.mm
ϴi = initial temperature of the conductor, °C
ϴf = final temperature of the conductor, °C

Note: strictly speaking ß is specified at 0 °C.  Within myCableEngineering calculations, ß is determined by taking the reciprocal of the 20 °C temperature coefficient.  This introduces a small, but negligible error. 

Typical Application

For manual calculations, the following will give realistic results:

    β [°C]    Qc [J.K-1.mm-3 ρ20 [Ω.mm]  
Copper 234.5 3.45 x 10-3 17.241 x 10-6
Aluminium 228 2.5 x 10-3 28.267 x 10-6
Steel 202 3.8 x 10-3 138 x 10-6

Substituting the above values and rearranging the IEC equation slightly, gives:

k=226 ln( 1+ θ f θ i 234.5+ θ i ) - copper conductors

k=148 ln( 1+ θ f θ i 228+ θ i ) - aluminium conductors

k=78 ln( 1+ θ f θ i 202+ θ i ) - steel

Comments

Energy Limiting Devices and I2t

Last updated on 2016-10-21 1 mins. to read

For details on thermal withstand and I2t, see I2t Thermal Withstand. Energy limiting devices reduce the I2t let-through in the event of a fault.  The values are typically specified by the manufacturer:

MCB Energy Limit

Typical MCB Energy Limiting Characteristic

Using typical data given above, for a 10A, 10kA fault rated MCB would have an Ip/A of 1000 (103), give an energy let-through of approximates 2,000 A2s.

 

Comments

I2t Thermal Withstand

Last updated on 2016-10-21 1 mins. to read

The thermal withstand of a cable can be determined by comparing the maximum energy at the fault, with the maximum energy the cable can absorb.  The equation for this is:

I2tk2A2

I2t is proportional to the energy let-through of the protective device
       I - fault current, A
       t - fault duration, S

k2A2 is proportional to the energy withstand of the cable
        k - adiabatic constant
        A - cable cross-sectional area, mm2

To better understand the theory behind the above, please see The adiabatic equation.

Comments

Non-adiabatic effects

Last updated on 2016-10-21 1 mins. to read

As mentioned, the adiabatic equation assumes no heat is dissipated from the cable during a fault.  While putting the calculation on the safe side, in some situations, particularly for longer fault duration there is the potential to be able to get away with a smaller cross section.  In these instances, it is possible to do a more accurate calculation.

Considering non-adiabatic effects is more complex.  Unless there is some driver, using the adiabatic equations is just easier.  Software is available to consider non adiabatic effects, however, there is a cost, time and complexity associated with this.

The IEC also publish a standard which deals with non-adiabatic equations:

  • IEC 60949 "Calculation of thermally permissible short-circuit current, taking into account non-adiabatic heating effects".

 

The method adopted by IEC 60949 is to use the adiabatic equation and apply a factor to cater for the non-adiabatic effects:

  I=ε I AD

where I - permissible short circuit current, A (or kA)
IAD - adiabatic calculated permissible short circuit current, A (or kA)
ε - factor to allow for heat dissipation from cable

The bulk of the IEC 60949 standard is concerned with the calculation of ε.

Comments

Shadi Abd Al Azim Feb 06, 2021 8:05 PM
Regarding copper wire screen, which factor i have to use 0.5 or 0.7?
which is better for short circuit rating copper wire screen and followed by tapes or covered by PVC?
what do IEC mean in sub clause 5.3.1 "the screen wires are fully surrounded by non—metallic materials."?
Steven McFadyen Feb 07, 2021 1:03 PM
Good point. The IEC clause is not overly clear.

I would interpret 5.3.1 as each screen wire individually surrounded by insulation.  Whereas in 5.3.2, the between-wire insolation is achieved by an air-gap.

Choose 0.7 or 0.5 depending on the situation you have in your cable.
Jhon M Jan 15, 2022 9:29 PM
Hello
Question please
Concerning short circuit current with combined copper wires screen and lead sheath (they are  in parallel, electrically connected ) and taking into consideration the non-adiabatic method

As per paragraph 6, to calculate the non adiabatic coefficient for screen/sheath, we need the thermal resistivity and volumetric heat capacity of materials that are under and over the screens

In this case, copper wire screen has Semi-conductor under it but lead sheath above it, and lead sheath has copper screen under it and PE outer sheath above it
How to do it in this case? Which thermal resistivity and volumetric heat capacity we need to consider for both copper screen and lead sheath which share the total short circuit current ?

We need to consider that the lead and copper are metals and have approx 0 thermal resistivity and in this case we take for copper screen the properties of SC layer and PE layer and for the lead the same? Is it correct?

to be more clear, if a screen has non metallic material under it but a metallic material above it like: XLPE/SC/CU WIRES/LEAD/PE
this case was not mentioned in IEC 60949
For CU wires, we need the  thermal resistivity and volumetric heat capacity of SC and PE or for SC and Lead for the formula ? and same in case of lead for combined screen ?

Is there anything else we need to take into consideration as we have here 2 sources of heat ? Thank u