Use the link on the left to access our cable sizing application. Manage and size all your cables, from low voltage to 33 kV.
G
2G
3G
4G
5G
6G
NR SBR
SiR
EPR
EVA
CR
CSM
Natural Rubber Styrol- Butadiene Rubber Compounds
Silicone Rubber
Ethylen- Propylene Rubber Compounds
Ethylene- Vinylacetate Copolymere Compounds
Poly- Chloroprene Compounds
Chloro- Sulfonated Polyethylene Compounds
Density g/cm3
1.5-1.7
1.2-1.3
1.3-1.55
1.3-1.5
1.4-1.65
1.3-1.6
Breakdown Voltage KV/mm (20oC)
20
30
25
Specific Volume Resistivity Ω cm (20oC)
1012-1015
1015
1014
1012
1010
Dielectric Constant 50 Hz (20oC)
3-5
3-4
3-3.8
5-6.5
6-8.5
6-9
Dielectric Loss Factor (tan δ)
1.9 x 10-2
6x 10-3
3.4 x 10-3
2 x 10-2
5 x 10-2
2.8 x 10-2
Working Temperature
Permanent oC
-65 +60
-60 +180
-30 +90
-30 +125
-40 +100
-30 +80
Short Time oC
+120
+260
+160
+200
+140
Melt Temperature +oC
-
Flame Resistance
Flammable
High Flash Point
Self Extinguishing
Oxygen Index LOI (% O2)
≤22
25-35
30-35
Heating Value H0 MJ.kg-1
21-25
17-19
19-23
14-19
Thermal Conductivity W.K-1.m-1
0.22
Corrosive Gases In Case Of Fire
No
Hydrogen Chloride
Radiation Resistance max Mrad
100
50
200
Tensile Strength N/mm2
5-10
8-12
10-20
Elongation At Break %
300-600
200-400
250-350
400-700
350-600
Shore Hardness
60-70 (A)
40-80 (A)
65-85 (A)
70-80 (A)
55-70 (A)
Abrasion Resistance
Moderate
Medium
Water Absorption %
1.0
1.5
Halogen Free
Yes
Weather Resistance
Good
Very Good
Cold Resistance