Cable Sizing

Earth Fault Loop Impedance for Cable Sizing

How earth fault loop impedance is calculated for cable sizing, including Zs, CPC impedance, BS 7671 disconnection checks and IEC 60909 sequence values.

Updated May 27, 2026

Earth fault loop impedance is the impedance of the path followed by earth-fault current from the source, through the line conductor, the fault, the protective conductor or return path, and back to the source. It determines how much fault current will flow and whether the protective device can disconnect within the required time.

The topic links directly to Circuit Protective Conductor (CPC) selection and Fault Current Calculations.

Earth fault loop impedance path diagram
Typical earth fault loop path, including external and cable impedance components.

Earth fault loop path

The earth fault loop impedance, Zs, is commonly represented as:

Zs=Ze+Z1+Z2
ZsEarth fault loop impedance, ohm
ZeExternal earth fault impedance, ohm
Z1Line conductor impedance, ohm
Z2CPC or return-path impedance, ohm

The external impedance depends on the upstream network. The CPC impedance depends on the protective conductor arrangement, such as armour, a separate conductor, trunking or another permitted metallic path.

BS 7671 disconnection requirements

BS 7671 uses earth fault loop impedance as part of automatic disconnection of supply. The protective device must operate within the required time for the circuit type and system earthing arrangement. Always confirm the applicable values against the current edition of the wiring regulations and the project specification.

System50 V < Uo ≤ 120 V a.c.50 V < Uo ≤ 120 V d.c.120 V < Uo ≤ 230 V a.c.120 V < Uo ≤ 230 V d.c.230 V < Uo ≤ 400 V a.c.230 V < Uo ≤ 400 V d.c.Uo > 400 V a.c.Uo > 400 V d.c.Other circuits, a.c. or d.c.
TN0.8 sNA0.4 s1 s0.2 s0.4 s0.1 s0.1 s5.0 s
TT0.3 sNA0.2 s0.4 s0.07 s0.2 s0.04 s0.1 s1.0 s

For TT circuits incorporating equipotential bonding in accordance with the relevant BS 7671 requirements, TN disconnection times may apply. For TN distribution circuits and circuits not covered by the table, a disconnection time not exceeding 5 s is generally permitted. For TT distribution circuits and other circuits not covered by the table, a time not exceeding 1 s is generally permitted.

For TN and TT systems, protective-device characteristics should satisfy:

Zs×IaU0×Cmin

For an IT system with a second fault, where the neutral or mid-point conductor is not distributed:

Zs×(2×Ia)U0×Cmin

Where an RCD is used for fault protection, the following condition is also relevant:

RA×IΔn50 V
IaCurrent causing operation of the protective device within the specified time, A
U0Nominal a.c. or d.c. line voltage to earth, V
CminMinimum voltage factor, typically 0.95
RASum of the earth electrode and protective conductor resistance, ohm
IΔnRated residual operating current of the RCD, A

External fault loop impedance

In myCableEngineering, the external earth fault loop impedance Ze is calculated in complex form using source earth-fault data entered by the user:

Ik2E=IE×pfEjIE×sin(cos1(pfE)) U=U03 Ze=UIk2E
IESource earth fault level, A
pfESource fault power factor
Ik2ESource earth fault current in complex form, A
UPhase voltage, V
U0Line-line voltage, V
ZeSource or external impedance, ohm

Cable loop impedance

myCableEngineering calculates positive and zero-sequence impedance in accordance with IEC 60909. For a line-to-earth short circuit, with Z2(60909) = Z1(60909), the fault current is:

Ik=3cUn|2Z1(60909)+Z2(60909)|

The common earth fault loop impedance terms can be related to IEC 60909 sequence values as follows:

EFL termIEC 60909 equivalent
ZeZe
Z1Z1(60909)
Z2, single-phase systemZ1(60909)
Z2, three-phase systemZ1(60909) + Z0(60909)

Total loop impedance and fault level

After the source and cable impedance components have been obtained, the total loop impedance and load-end fault current are:

Zt=Ze+Z1+Z0 If=UZt

The earth fault loop impedance is the magnitude of Zt. For common configurations, myCableEngineering calculates a maximum allowable earth fault loop impedance, although this can be overridden by the user. For other configurations, the required maximum value should be entered by the user.

CPC and protective device checks

The cable armour may be used as the CPC in the calculation of zero-sequence impedance and earth fault loop impedance. The user may also add an additional conductor in parallel with armour to form the CPC, either internal or external to the cable.

Protective conductor sizing should be checked against the relevant wiring regulation, including minimum sizes and thermal withstand. Protective-device settings and any RCD settings must also be checked to confirm the required disconnection condition is met.

For related topics, see Circuit Protective Conductor (CPC), Fault Current Calculations and Cable Thermal Withstand.

For the broader IEC 60909 short-circuit formula set, see IEC 60909 Fault Calculations.

For converting external fault level data into source impedance, see Network Fault Level.

For the positive and zero sequence cable impedance formulae behind loop calculations, see Cable Impedance.

Related Articles