Halogen-Free Cable Compounds: Properties and Comparison

A comparison of halogen-free cable compounds, including non-cross-linked and cross-linked polymer properties for LSZH cable designs.

Updated May 27, 2026

Halogen-free cable compounds are used where the fire behaviour of the cable is important, especially where corrosive gases and smoke toxicity need to be reduced. These compounds are commonly associated with LSZH cable designs.

The table below compares typical properties for non-cross-linked and cross-linked halogen-free polymer compounds. Values are indicative and should be checked against the manufacturer’s datasheet for the actual cable compound being specified.

Halogen-free compound comparison

PropertyH
Not cross-linked halogen-free polymer compounds
HX
Cross-linked halogen-free polymer compounds
Density, g/cm31.4-1.61.4-1.6
Breakdown voltage, kV/mm at 20 °C2525
Specific volume resistivity, Ω cm at 20 °C1012-10141013-1014
Dielectric constant, 50 Hz at 20 °C3.4-53.4-5
Dielectric loss factor, tan δ~10-310-2-10-3
Permanent working temperature, °C-30 to +70-30 to +90
Short-time temperature, °C+100+150
Melt temperature, °C>130–
Flame resistanceSelf-extinguishingSelf-extinguishing
Oxygen index, LOI (% O2)≤40≤40
Heating value H0, MJ/kg17-2216-25
Thermal conductivity, W/(K·m)0.170.20
Corrosive gases in case of fireNoNo
Radiation resistance, max Mrad100200
Tensile strength, N/mm28-138-13
Elongation at break, %150-250150-250
Shore hardness65-95 (A)65-95 (A)
Abrasion resistanceMediumMedium
Water absorption, %0.2-1.50.2-1.5
Halogen freeYesYes
Weather resistanceMedium; good in black compoundsMedium; good in black compounds
Cold resistanceAverageAverage

When halogen-free compounds are useful

Halogen-free compounds are often selected for buildings, tunnels, public areas, transport systems, control rooms and other locations where reduced corrosive gas emission is important during a fire.

Material selection should consider the whole cable system, including required operating temperature, flame performance, smoke requirements, mechanical strength, installation environment and any CPR or project-specific fire performance classification.

   