Cable Sizing

IEC 60909 Fault Calculations: Short-Circuit Current Formulae

IEC 60909 short-circuit current formulae for three-phase, single-phase and DC fault calculations, including voltage factor and source impedance.

Updated May 27, 2026

IEC 60909 gives a method for calculating short-circuit currents in three-phase a.c. systems. It is commonly used to estimate maximum and minimum fault levels for switchgear rating, protection settings and cable withstand checks.

This article summarises the formulae used for faults far from generators. It sits under the wider Fault Current Calculations topic and links to Earth Fault Loop Impedance where IEC 60909 sequence values are used in cable calculations.

Short-circuit current formulae

For most components other than synchronous machines, the negative sequence impedance Z2 can often be taken as equal to the positive sequence impedance Z1.

Fault typeThree-phase systemSingle-phase systemD.C. system
Three-phase short circuitIk=cUn3Z1
Line-to-line short circuitIk2=cUnZ1+Z2=cUn2Z1=32IkIk=cUn3×2Z1Ik=cUn2Z1
Line-to-line-earth short circuitIkE2E=3cUnZ2Z1Z2+Z1Z0+Z2Z0=3cUnZ1+2Z0
Line-earth short circuitIk1=3cUnZ1+Z2+Z0=3cUn2Z1+Z0Ik=cUn3(Z1+Z0)Ik=cUnZ1+Z0

For a single-phase system, a line-to-line fault is equivalent to a line-neutral fault. For a d.c. system, it is equivalent to a positive-to-negative fault.

For several series circuits in the fault loop, the final fault current can be calculated from the sum of the series impedances:

Ik=cUn3iZi

For d.c. circuits:

Ik=cUniZi

Source impedance

The source or external network impedance ZQ can be calculated from the short-circuit current. For three-phase and single-phase systems:

ZQ=cUn3Ik

For d.c. systems:

ZQ=cUnIk

Maximum and minimum fault levels

Both maximum and minimum fault levels are normally required. Maximum fault current is used for equipment short-circuit ratings. Minimum fault current is used to confirm that protective devices operate correctly under the least favourable fault condition.

  • Use cmax or cmin as appropriate.
  • When calculating external network impedance ZQ, use the maximum or minimum short-circuit current as appropriate.
  • IEC 60909 recommends resistance at 20 °C for maximum short-circuit current, and resistance at end-of-short-circuit temperature for minimum short-circuit current.
  • User-entered fault levels are commonly treated as values with voltage factor c = 1.

In myCableEngineering, conductor operating temperature is used as the reference for both maximum and minimum fault levels.

Voltage factor

Nominal voltage Uncmax for maximum short-circuit currentcmin for minimum short-circuit current
Low voltage, 100 to 1000 V1.050.95
Medium voltage, 1 kV to 33 kV1.101.00
High voltage, above 35 kV1.101.00

Symbols

cVoltage factor
IkInitial symmetrical three-phase short-circuit current, r.m.s., A
Ik1Line-to-earth short-circuit current, A
Ik2Line-to-line short-circuit current, A
IkE2ELine-to-line-earth short-circuit current, A
UnNominal system voltage, line-to-line r.m.s., V; positive-negative voltage for d.c. systems
Z1Positive-sequence short-circuit impedance, ohm
Z2Negative-sequence short-circuit impedance, ohm
Z0Zero-sequence short-circuit impedance, ohm
ZQImpedance of an external network, ohm

For converting upstream fault level data into source impedance, see Network Fault Level.

For estimating a transformer secondary source fault level before IEC 60909 network calculations, see Transformer Secondary Fault Level.

For the cable sequence impedance inputs used by IEC 60909, see Cable Impedance.

Related Articles